LV XLPE Insulated Aerial Bundled Cables 234 Core Copper

Physical Data
Nominal conductor area
mm2
Number and nominal diameter of wires no/mm Nominal conductor diameter mm Average insulation thickness mm Nominal diameter over insulation mm Nominal diameter over laid-up cores
mm
Approx. mass kg/km
2 Core
6 7/1.04 3.1 1.3 5.8 11.7
10 7/1.35 4.1 1.3 6.8 13.5 230
16 7/1.70 5.1 1.3 7.8 15.6 350
3 Core
6 7/1.04 3.1 1.3 5.8 12.6 220
10 7/1.35 4.1 1.3 6.8 14.6 340
16 7/1.70 5.1 1.3 7.8 16.9 520
4 Core
7/1.04 3.1 1.3 5.8 14.1 290
10 7/1.35 4.1 1.3 6.8 16.3 460
16 7/1.70 5.1 1.3 7.8 18.9 690
Performance Data
Nominal conductor resist area
mm2

DC

at 20°C Ω/km

AC resist . at 50Hz 80°C Ω/km Inductive reactance at 50Hz Ω/km Voltage drop at 50Hz 80°C mV/A.m Continuous current rating, A

Fault current

rating kA for 1s

Minimum bending radius (installed) mm

Min.

breaking load of cable

kN

Rec. tension Modulus of elasticity Gpa Coeff. of linear expansion 10 –6/°C

Still

air

1m/s wind 2m/s wind Core Cable Highest everyday tension kN Max working tension kN
2 Core
6 3.17 3.18 0.11 7.79 36 56 66 0.8 25 70 4.6 0.84 1.3 112 17
10 1.88 1.89 0.098 4.62 48 77 90 1.4 25 80 7.8 1.41 2.2 112 17
16 1.18 1.19 0.092 2.91 64 100 120 2.2 30 95 11.8 2.13 3.32 112 17
3 Core
6 3.17 3.89 0.11 7.79 32 54 62 0.8 25 75 7 1.25 1.95 112 17
10 1.88 2.31 0.098 4.62 44 73 84 1.4 25 90 11.8 2.12 3.29 112 17
16 1.18 1.45 0.092 2.91 58 96 110 2.2 30 100 17.8 3.2 4.97 112 17
4 Core
6 3.17 3.89 0.11 6.75 32 54 62 0.8 25 85 9.3 1.67 2.6 112 17
10 1.88 2.31 0.11 4 44 73 84 1.4 25 100 15.7 2.82 4.39 112 17
16 1.18 1.45 0.1 2.52 58 96 110 2.2 30 110 23.7 4.26 6.63 112 17
ISO 9001:2015 JAS- ANZ brust-pucker
Power Systems brust-pucker
Tele Communication Systems brust-pucker
IEC Standard 61300-3-3--5 brust-pucker
Quality Management brust-pucker
Quality Control brust-pucker